One pre-insulated weather-proof impulse tube RizurPak-S
RizurPak-S – is an efficient, reliable, and cost effective solution for small diameter tubing lines insulation and required temperature maintenance along the whole length of the impulse lines and pipelines.
RizurPak-S system has non-hygroscopic fiberglass as insulation and an outer housing made of thermoplastic polyester urethane elastomer stabilized hydrolitically.
Application areas:
- steam supply
- condensate recirculation
- water purification
- chemicals dosing
Design variants of RizurPak-S are different in diameter, weight, and size of the process pipe.
Dimensions |
Nominal weight kg/m | Nominal dimensions (diameter), mm |
|
RizurPak-S One 6 mm process pipe |
0,45 | 28 | |
RizurPak-S One 8 mm process pipe | 0,6 | 33 | |
RizurPak-S One 10 mm process pipe | 0,74 | 36 | |
RizurPak-S One 12 mm process pipe | 0,6 | 33 |
Accessories and components
For connection and installation of the pre-insulated impulse tubing bundles to the pipelines, technical process and devices the following equipment can be used:Silicone insulation
Black silicone insulator RTV used for hermetization of both ends of the tubing bundle for protection against moisture penetration.
Input device for the tubing bundles RizurPak
Input device for the tubing bundle RizurPak provides waterproof insulation in the place of tubing bundle RizurPak entering the enclosure, for example, through a wall. The input device for the tubing bundle RizurPak consists of a set of rings and a heat-shrinking cap for tubing bundle insulation.
Heat shrink tape sleeve
Heat shrink tape sleeves ensure insulation of the ending part of RizurPak that protects the system against climatic factors impact. The material used is thermally stabilized modified polyolefin. It’s recommended to use heat shrink tape sleeves for all the open endings of the tubing bundle. This sealing method provides the best protection against climatic factors impact.
Repair kit for the housing
The repair kit for the housing is used for sealing the connections in the tubing bundle or for the elongation of the insulation layer and the housing that protects the system against climatic factors in cases when during installation the cut piece was too long or if there’s a need to join two tubing bundle cuts. The materials in the kit are used for any repairs of tubing on-site. The repair kit is necessary when mounting an additional thermostat for temperature control of the process tubing. Each kit has a thermal insulation material, fiberglass tape, and a self-sealing patch.
ThermoregulatorsThe repair kit for the housing is used for sealing the connections in the tubing bundle or for the elongation of the insulation layer and the housing that protects the system against climatic factors in cases when during installation the cut piece was too long or if there’s a need to join two tubing bundle cuts. The materials in the kit are used for any repairs of tubing on-site. The repair kit is necessary when mounting an additional thermostat for temperature control of the process tubing. Each kit has a thermal insulation material, fiberglass tape, and a self-sealing patch.
RIZUR-TB-DCS manufactured by NPO RIZUR can be used for temperature control in the process lines.
Thermostats
Used for temperature control in the process lines.
A set of heat shrink tape sleeves for high-temperature heating cables
The set complies with the CENELEC and GOST-R standards for operation in the hazardous areas. It's used with tracers MN and N15 or N20 of any capacity.
A set of heat shrink tape sleeves for low-temperature heating cables
The set complies with the CENELEC and GOST-R standards for operation in the hazardous areas. It can be used with tracers of any capacity.
A kit for connecting the heating cable to the power supply network
The kit consists of a cable gland and a set of heat shrink tape for installation inside the terminal box with M25 thread. It complies with CENELEC and GOST-R standards for use in hazardous areas. It can be used with tracers P, MN, and N15 or N20 of any capacity.
Technical specifications
Installation area | General industrial areas |
Areas exposed to explosion hazards V-1a and V-1d, acc. to Electrical installation code (PUE), Ch. 7.3 | |
Resistivity | to oil products |
to chemical environments | |
to ultraviolet radiation | |
Explosion-proof marking: | |
RizurPak-E Series | 1 Exs II T6…T4 X* |
RizurPak-L/-H/-S Series | II Gb T6…T4 X* |
Ingress protection | - IP67 acc. to GOST 14254-96 |
Min. ambient temperature for installation | -40°С |
Ambient temperature range for installation: | |
for the temperature rating Т6 | -70 ... +45 °С |
for the temperature rating Т5 | -70 ... +60 °С |
for the temperature rating Т4 | -70 ... +95 °С |
for the temperature rating Т3* | -70 ... +160 °С |
for the temperature rating Т2* | -70 ... +255 °С |
for the temperature rating Т1* | -70 ... +405 °С |
Max temperature of the housing surface | +60° С |
Supply voltage for RIZURPAK-E | 230V |
Housing colour | any (black on default) |
Warranty period | 12 months |
24/36 months (on request) | |
Average operation time | over 20 years |
Technical specification of RizurPak materials
Housing |
Thermoplastic polyester urethane elastomer stabilized by a hydrolytic method: • does not contain halogens; • resistant to abrasive impacts; • resistant to UV radiation; • maintains flexibility at low temperatures |
Insulation | Non-hygroscopic fiber-glass |
Temperature | |
• RizurPak-L, H, S | Max. temperature of the process line - 204°C* |
• RizurPak-E |
Constant temperature: XTV 121°C* BTV 65°C* Short-term temperature: XTV 250°C* BTV 85°C* Max. temperature of the tracing: XTV temp. rating T3, 230°C BTV temp. rating T6, 85°C |
Technical specifications of the tube
Outside diameter, mm |
Wall, mm |
Construction and material | ASTM |
6
|
1 | seamless calibrated 316/316L SS | А-269 |
8 | 1 | seamless calibrated 316/316L SS | А-269 |
10 | 1 | seamless calibrated 316/316L SS | А-269 |
12 | 1 | seamless calibrated 316/316L SS | А-269 |
12 | 1,5 | seamless calibrated 316/316L SS | А-269 |
14 | 1 | seamless calibrated 316/316L SS | А-269 |
14 | 1,6 | seamless calibrated 316/316L SS | А-269 |
14 | 2 | seamless calibrated 316/316L SS | А-269 |
6 | 1 | copper | В-68, В-75 |
8 | 1 | copper | В-68, В-75 |
10 | 1 | copper | В-68, В-75 |
12 | 1 | copper | В-68, В-75 |
6 | 1 | 6 mm PFA Teflon |
|
8 | 1 | 8 mm PFA Teflon |
|
10 | 1 | 10 mm PFA Teflon |
|
12 | 1 | 12 mm PFA Teflon |
|